Commercial Building AHU Temperature Control & Energy Monitoring: BACnet/IP Edge IO Controller BA190
Categories

Commercial Building AHU Temperature Control & Energy Monitoring: BACnet/IP Edge IO Controller BA190

A 12-story office needs 8 AHUs integrated into a Honeywell BMS. Lacking temp feedback, AO modules, and fast freeze protection, the conventional PLC+gateway approach is complex. The BA190 replaces both with native BACnet/IP, modular I/O, and local logic—cutting cost, setup time, and failure points.
Commercial Building AHU Temperature Control & Energy Monitoring: BACnet/IP Edge IO Controller BA190
Case Details

Scenario

  • A 12-story office building with 8 fresh air handling units (AHUs) needs to be integrated into a Honeywell BMS. Site conditions:
  • Control panels have only DO for start/stop, no supply/return air temperature feedback.
  • Water valves are 0-10V actuators, but no AO module available on site.
  • Floor-by-floor power meters use Modbus RTU; energy data must be brought into the BMS for cost allocation.
  • When a freeze thermostat trips, the fan must stop and the water valve close within 100ms – this cannot rely on the network.

Conventional approach: PLC + BACnet gateway. Two devices, two software tools, two debugging efforts. If the gateway mapping table doesn’t match, you have to modify code on site.

The BA190 solves it with a single device.

Why BA190

  • Native BACnet/IP uplink: Device ID, object instances, COV subscription are all native. The BMS discovers the device automatically – no gateway required.
  • Modular I/O: 1 to 3 I/O boards, flexible combination. This AHU needs: 2 AI (PT1000 supply/return air temperature), 1 AO (0-10V water valve), 4 DI (freeze thermostat, filter differential pressure, manual/auto mode, fault alarm), 1 DO (fan start/stop).
  • Built-in logic independent of the host: Freeze protection interlocking runs locally on the device, responding in milliseconds even if the network fails.

Real-World Benefits

  • Hardware cost: PLC+gateway→ BA190 – save over 70% .
  • Labor hours: 1 day for PLC programming + 0.5 day for gateway configuration → 2 hours of web-based configuration.
  • Failure points: Eliminates one gateway; fewer protocol conversions, easier troubleshooting.

When to Use BA190 (Replaces "PLC + Gateway")

  • You have DI, DO, AI, AO that need to be brought into a BACnet/IP network.
  • You need local interlocking (freeze protection, differential pressure, liquid level).
  • You have Modbus instruments (power meters, water meters, energy meters) that need to be converted to BACnet.
  • You want to reduce device types and shorten on-site commissioning time.
  • If you also need to send data to the cloud (MQTT/OPC UA/Modbus TCP), choose the BA190Pro.

Tell us your I/O requirements and we will help you select the right Y series module combination. We look forward to discussing your next project.

Leave a message
FirstName*
LastName*
Email*
Message*
Code*
Verification Code
We use Cookie to improve your online experience. By continuing browsing this website, we assume you agree our use of Cookie.